Requirements for Particular Spaces

Requirements for Particular Spaces
E.1 Accommodation spaces
As far as applicable, national requirements should be observed concerning primary data of air condition
system and air change rates.
E.2 Galleys
E.2.1 Where they pass through accommodation spaces or spaces containing combustible materials,
the exhaust ducts from galley ranges shall be constructed of insulated "A" class divisions. Each exhaust
duct shall be fitted with:
 a grease trap readily removable for cleaning
 a fire damper located in the lower end of the duct and in addition, a fire damper in the upper end of
the duct
 arrangements, operable from within the galley near exit, for shutting off the exhaust fan
 fixed means for extinguishing a fire within the duct are to be provided on all cargo ships and passenger
vessels carrying not more than 36 passengers, where the ducts pass through accommodation
spaces or spaces containing combustible materials